Publication: Predictive factors of Legionella pneumophila contamination in cooling tower water
dc.contributor.author | Pipat Lluksamijarulkul | en_US |
dc.contributor.author | Sumawadee Kornkrerkkiat | en_US |
dc.contributor.author | Cchayaporn Saranpuetti | en_US |
dc.contributor.author | Ddusit Sujirarat | en_US |
dc.contributor.other | Mahidol University | en_US |
dc.date.accessioned | 2018-11-09T02:18:43Z | |
dc.date.available | 2018-11-09T02:18:43Z | |
dc.date.issued | 2014-01-13 | en_US |
dc.description.abstract | A cross-sectional study of 160 water samples collected from 72 cooling towers in 4 hospitals, 7 department stores, and 3 hotels in Bangkok was carried out to investigate Legionella pneumophila contamination and its predictive factors. All water samples were cultured for Legionella spp. and tested for L. pneumophila by real-time polymerase chain reaction (PCR). Some cooling tower parameters were measured and recorded. Data were analyzed using χ2-test, odds ratio and stepwise logistic regression analysis at the significant level of α = 0.05. Results revealed that the Legionella spp. contamination was 20.0% (32/160) and for L. pneumophila was 61.3% (98/160). The sensitivity of real-time PCR was higher than that of the culture. Factors significantly asso-ciated with L. pneumophila contamination by χ2-test were: the cooling tower model, size, use duration, pH, water temperature, use of ozone, and residual free chlorine (95% CI of OR > 1.0, P < 0.05). After stepwise logistic regression analysis, four predictive factors remained. These included the cooling tower model being a cross-flow type (adjusted OR = 3.1, 95% CI = 1.2-7.8, P = 0.017), use duration > 5 years (adjusted OR = 3.6, 95% CI = 1.3-10.1, P = 0.016), water temperature < 29.4°C (adjusted OR = 7.9, 95% CI = 2.1-29.6, P = 0.002), and residual free chlorine < 0.2 ppm (adjusted OR = 8.5, 95% CI = 2.1-34.9, P = 0.003). Additionally, the risk probability for L. pneumophila contamination was estimated to be 13.9-97.1%, depending on the combination of predictive factors. © the authors, publisher and licensee Llibertas Academica Llimited. | en_US |
dc.identifier.citation | Air, Soil and Water Research. Vol.7, (2014), 11-17 | en_US |
dc.identifier.doi | 10.4137/ASWRr.S12972 | en_US |
dc.identifier.issn | 11786221 | en_US |
dc.identifier.other | 2-s2.0-84892616808 | en_US |
dc.identifier.uri | https://repository.li.mahidol.ac.th/handle/20.500.14594/33913 | |
dc.rights | Mahidol University | en_US |
dc.rights.holder | SCOPUS | en_US |
dc.source.uri | https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=84892616808&origin=inward | en_US |
dc.subject | Environmental Science | en_US |
dc.title | Predictive factors of Legionella pneumophila contamination in cooling tower water | en_US |
dc.type | Article | en_US |
dspace.entity.type | Publication | |
mu.datasource.scopus | https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=84892616808&origin=inward | en_US |